Trimm 8273221001 Fuse Panel GMT/TPA Fuse Panel ±24-48V DC

(No reviews yet) Write a Review
SKU:
8273221001
Availability:
This item currently has a 12 week lead time
$1,564.00
Frequently bought together:

Description

Trimm 8273221001 Fuse Panel GMT/TPA Fuse Panel ±24-48V DC

General

  • Dimensions: 19.00” W x 3.50” H x 12.125” D
  • Rack Space: 2U
  • Weight: 11.0 lbs.
  • Mounting: Universal 19” or 23”, WECO or EIA
  • Mounting Position: Flush, 3” or 4” Offset
  • Finish: Black Textured Powder Coat


Electrical

Input:

  • Nominal Voltage: -/+24-48V DC
  • Voltage Range: -/+19-60V DC
  • Number of Buses: 2
  • Intr. Device Rating: 375 Amps


Output:

  • Max Fuse Rating/; TPA Fuse - 50 Amp/GMT Fuse - 15 Amp
  • Continous Load Rating: TPA Fuse - 40 Amps/GMT Fuse - 10.5 Amps

ALARMING

  • Indicators: Green (Power)/Red (Alarm)
  • Function: Form C relay contacts for remote fuse and power fail indication
  • Conn. Type: Solderless Wire Wrap (18 to 30 AWG)
  • Rating: DC 30W/AC 50VA

Connections

Input:

  • 2 Hole Lug: 3/8’’ stud x 1’’ spacing
  • Wire Range: Up to 500 kcmil
  • Max. Terminal: Width 1.400”
  • Tightening Torque: 190 in-lb (21.5 Nm)


Output:

  • TPA - Barrier Strip/GMT - Set Screw: TPA - #8 SEMS Screw./GMT - Cage Clamp
  • Wire Range: TPA - 6 to 22 AWG GMT - 10 to 22 AWG
  • Max. Terminal Width: TPA - .500” / GMT - Not Needed
  • Tightening Torque: 5 in-lb GMT - 16 in-lb TPA

Ground Bus:

  • 2 Hole Lug: 1/4” stud x 1” spacing
  • Wire Range: 2 AWG lug supplied with panel

Environment

  • Short Term Op Temp: -40° C to +70° C
  • AmbientL Up to 65° C
  • Store TempL -40° C to +70° C
  • HumidityL 0 to 95% non-condensing
  • Power Dissipation: 82.8 Watts max

Standards

  • Safety(Listed): UL 60950-1/UL 1801/CSA C22.2 No.60950-1/EN 60950-1/IEC 60950-1
  • Telcordia: NEBS Level 3 (GR-63/GR-1089) and GR-3108 Class 3 (w/o salt fog testing)

This product comes with manufacturer's warranty.

DOWNLOAD DATA SHEET HERE

View AllClose